Applications: Frequency converters for motor drives, wind power installations and power supply units
When electronic components are panel-mounted in a cabinet, in the most of the cases the same circuits with different power are required.To avoid pemanent modifications of the apertures, several power ranges should ideally be combined. The filters of this series, within the most important power range, have equal fixing dimenions, so that the filters can be replaced.
Type |
Rated voltage [V] |
Rated current [A] |
Leakage current [mA] |
Cx [µF] |
Cy [nF] |
L [mH] |
R [kOhm] |
CNW 114/8 |
|
3x8 |
<16 |
1,0 |
0,2 |
7,6 |
560 |
CNW 114/16 |
|
3x16 |
<16 |
2,5 |
1,6 |
5,2 |
560 |
CNW 114/25 |
|
3x25 |
<180 |
2,5 |
1,6 |
2,5 |
560 |
CNW 114/36 |
|
3x36 |
<180 |
2,5 |
1,6 |
1,5 |
560 |
CNW 114/50 |
|
3x50 |
<180 |
2,5 |
1,6 |
0,9 |
560 |
CNW 114/64 |
|
3x64 |
<180 |
2,5 |
1,6 |
0,9 |
560 |
CNW 114/80 |
3 x |
3x80 |
<200 |
3,7 |
2,4 |
0,8 |
560 |
CNW 114/110 |
500/ 690 |
3x110 |
<200 |
3,7 |
2,4 |
0,5 |
560 |
CNW 114/180 |
|
3x180 |
<220 |
3,7 |
2,4 |
0,5 |
560 |
CNW 114/280 |
|
3x280 |
<260 |
7,2 |
4,6 |
0,3 |
560 |
CNW 114/300 |
|
3x300 |
<260 |
7,2 |
4,6 |
0,3 |
560 |
CNW 114/450 |
|
3x450 |
<760 |
7,6 |
4,75 |
0,11 |
560 |
CNW 114/600 |
|
3x600 |
<760 |
7,6 |
4,75 |
0,11 |
560 |
CNW 114/900 |
|
3x900 |
<760 |
7,6 |
4,75 |
0,05 |
560 |
CNW 114/1200 |
|
3x1200 |
<760 |
7,6 |
4,75 |
0,05 |
560 |
Type |
Housing |
Connection |
PE-Connection |
B1 |
B2 [mm] |
B3 [mm] |
D [mm] |
E [mm] |
H [mm] |
L1 [mm] |
L2 [mm] |
L3 [mm] |
CNW 114/8 |
B/SR |
Terminals 4 mm2 |
Earthing bolt (M6) |
115 |
100 |
85 |
6,2 |
- |
60 |
202 |
180 |
115 |
CNW 114/16 |
B/SR |
Terminals 4 mm2 |
Earthing bolt (M6) |
150 |
136 |
120 |
6,2 |
- |
65 |
222 |
200 |
115 |
CNW 114/25 |
B/SR |
Terminals 6 mm2 |
Earthing bolt (M6) |
150 |
136 |
120 |
6,2 |
- |
65 |
229 |
200 |
115 |
CNW 114/36 |
B/SR |
Terminals 10 mm2 |
Earthing bolt (M6) |
150 |
136 |
120 |
6,2 |
- |
65 |
229 |
200 |
115 |
CNW 114/50 |
B/SR |
Terminals 10 mm2 |
Earthing bolt (M6) |
150 |
136 |
120 |
6,2 |
- |
65 |
229 |
200 |
115 |
CNW 114/64 |
B/SR |
Terminals 16 mm2 |
Earthing bolt (M6) |
150 |
136 |
120 |
6,2 |
- |
65 |
238 |
200 |
115 |
CNW 114/80 |
C/SR |
Terminals 25 mm2 |
Earthing bolt (M10) |
170 |
130 |
- |
8,5 |
- |
90 |
400 |
373 |
350 |
CNW 114/110 |
C/SR |
Terminals 50 mm2 |
Earthing bolt (M10) |
170 |
130 |
- |
8,5 |
- |
90 |
400 |
373 |
350 |
CNW 114/180 |
C/SR |
Terminals 95 mm2 |
Earthing bolt (M10) |
180 |
156 |
- |
10,0 |
- |
115 |
510 |
470 |
360 |
CNW 114/280 |
C/SR |
Terminals 150 mm2 |
Earthing bolt (M10) |
260 |
220 |
- |
12,0 |
- |
130 |
700 |
660 |
530 |
CNW 114/300 |
C/SR |
Terminals 150 mm2 |
Earthing bolt (M10) |
260 |
220 |
- |
12,0 |
- |
130 |
700 |
660 |
530 |
CNW 114/450 |
D/SR |
Bars (25x8) |
Earthing bolt (M12) |
300 |
275 |
250 |
9,0 |
10,5 |
160 |
610 |
516 |
210 |
CNW 114/600 |
D/SR |
Bars (30x8) |
Earthing bolt (M12) |
300 |
275 |
250 |
9,0 |
10,5 |
160 |
630 |
516 |
210 |
CNW 114/900 |
D/SR |
Bars (50x10) |
Earthing bolt (M12) |
300 |
275 |
250 |
9,0 |
13,0 |
160 |
716 |
516 |
210 |
CNW 114/1200 |
D/SR |
Bars (60x10) |
Earthing bolt (M12) |
300 |
275 |
250 |
9,0 |
13,0 |
160 |
716 |
516 |
210 |